Ideal transformer at kV primary and household secondary voltage serving a resistive load: load resistance

The same question, asked 2 times: 28 Jul 2022*, 6 Apr 2023. Every wording below, oldest first.

Try each one first, then open its answer.

  1. Question 1

    28 Jul 2022

    104
    A transformer operating at primary voltage 8kV8kV and secondary voltage 160 V160\text{ }V serves a load of 80 kW80\text{ }kW. Assuming the transformer to be ideal with purely resistive load and working on unity power factor, the loads in the primary and secondary circuit would be

    Tap an option to check your answer.

  2. Question 2

    6 Apr 2023

    28
    An ideal transformer with purely resistive load operates at 12kV12kV on the primary side. It supplies electrical energy to a number of nearby houses at 120 V120\text{ }V. The average rate of energy consumption in the houses served by the transformer is 60 kW60\text{ }kW. The value of resistive load (Rs) required in the secondary circuit will be ___mΩ\_\_\_ m\Omega.